PowerBox8 Specification Notes • FL • 3000psi
Specification Notes
Florida Product Approval Number FL11383 – Power Box
Click here to download printable PowerBox Engineering Package (PDF)
Gravity
Lateral/Uplift
NOTES: PowerBox8 Gravity – 16 and 20 Gauge
Florida - 3000psi
- PRODUCT NAME;PREFORMED POWERS STEEL LINTEL SHALL BE GALVANIZED COIL STEEL AS MANUFACTURED BY POWERS STEEL AND WIRE PRODUCTS, INC. STEEL GRADE SHALL BE ASTM A570 GRADE C (FY= 40 ksi).NOTE: DEFORMATIONS DO NOT EFFECT STRUCTURAL CAPACITY. FOR SPANS LESS THAN 16'-0" BOX LINTELS TO BE 20 GA. FOR SPANS GREATER THAN OR EQUAL TO 16'-0" BOX LINTELS TO BE 16 GA.
- SHORE LINTELS AS REQUIRED TO COMPENSATE FOR DEAD LOAD DEFLECTION ON NON-CURED MASONRY GROUT. ALL LINTELS GREATER THAN 18'-0" ARE BUILT WITH 1/2" CAMBER.
- LINTEL TO BE USED WITH BRICK OR CONCRETE MASONRY UNITS HAVING MINIMUM f’m AS SHOWN.
- STEEL SURFACES IN CONTACT WITH GROUT AND/OR MORTAR SHALL BE UNPAINTED AND FREE OF MATERIAL THAT MIGHT INHIBIT BOND.
- DESIGN BEARING OF POWERS STEEL LINTELS IS 8" FOR ALL LINTELS GREATER THAN 18'-0" IN SPAN OR GREATER THAN 32" IN DEPTH. ALL OTHER LINTELS REQUIRE A MINIMUM OF 4" BEARING PER THE STANDARD AND FLORIDA BUILDING CODES.
- f’m = 1500 psi. MASONRY UNITS SHALL CONFORM TO ASTM C90, GRADE N.
- GROUT = 3,000 psi. SLUMP RANGE: 8" TO 11". ROD OR VIBRATE GROUT ADEQUATELY TO ENSURE CONSOLIDATION OF GROUT (NO AIR POCKETS). GROUT SHALL COMPLY WITH ASTM C476-83 AND BE EITHER COARSE OR FINE GROUT.
- MORTAR: TYPE “S” OR TYPE “M” 1800 psi.
- TOP REINFORCING OR TOP OF WALL REINFORCING, IS REQUIRED BY CODES TO PROVIDE A CONTINUOUS TIE AROUND A STRUCTURE AND TO PROVIDE FOR UPLIFT RESISTANCE AT LINTELS.
- ATTACHMENTS TO TOP OF WALL PER ARCHITECTURAL AND/OR ENGINEERING DRAWINGS.
- LIMITATIONS:THE LINTELS SHALL NOT EXCEED THE ALLOWABLE DESIGN LOADS AND SPANS SHOWN IN THIS REPORT.THE LINTELS SHALL NOT BE USED IN A FIRE RESISTANCE RATED ASSEMBLY UNLESS A TEST REPORT DOCUMENTING FIRE RESISTANCE IS SUBMITTED TO THE BUILDING OFFICIAL.A PROPER BARRIER IS REQUIRED WHEN USING CORROSIVE LUMBER PRODUCTS IN CONTACT WITH THE STEEL LINTELS. A PROPER BARRIER WOULD BE A POLYETHYLENE BARRIER WITH A 10 MIL THICKNESS OR TO MAINTAIN A MIN. 1/4" SPACING BETWEEN THE CORROSIVE LUMBER AND STEEL LINTEL.
- DEFLECTION LIMITS ARE SET TO L/600 FOR ALL LOADS SHOWN ABOVE THE DARKENED SOLID LINE. DEFLECTION LIMITS ARE SET TO L/360 [LIVE LOAD] AND L/240 [DEAD + LIVE LOAD] FOR ALL LOADS SHOWN BELOW DARKENED SOLID LINE.
- ALL LOADS SHOWN IN TABLES ARE SUPERIMPOSED LOADS. TABLES ARE DATED 01/2021 AND CLEARLY INDICATE SUPERIMPOSED LOADS.
- #5 REINFORCING BAR(S) GRADE 40 ARE TO SET APPROX. 1-1/2" FROM TOP OF ALL LINTEL DESIGNS AND IN SOME CASES THE BOTTOM OF LINTEL AS SHOWN ON LOAD TABLES. TOP HORIZONTAL REINFORCEMENT IS TO BE A CONTINUOUS TIE AS NOTED IN NOTE #9. IN THE CASE THAT THE LINTEL IS NOT WITHIN A COMPOSITE BOND BEAM SYSTEM, TOP HORIZONTAL REINFORCEMENT IS TO EXTEND 2'-0" PAST INSIDE OF JAMBS.
- MANUFACTURER:POWERS STEEL 4118 E. ELWOOD PHOENIX, AZ 85040PH# (602) 437-1160
- TECHNICAL DATA AND ENGINEERING POWERS LINTELS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE FOLLOWING:+ FLORIDA BUILDING CODE - 2020 (SEVENTH EDITION)+ AISI NORTH AMERICAN SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL - 2016+ TMS 402-16TECHNICAL ASSISTANCE IS AVAILABLE FROM THE MANUFACTURER ON SPECIAL DESIGN CONCERNS OR LINTEL DEPTHS DIFFERENT THAN THOSE SHOWN IN THE LOAD TABLES.STRUCTURAL ENGINEER FOR THESE LINTELS IS: S.E. CONSULTANTS, INC. 5800 E. THOMAS RD. SUITE 104 SCOTTSDALE, AZ 85251 PHONE (480) 946-2010 FAX (480) 946-1909 IF AN INSPECTOR, CONTRACTOR, SUBCONTRACTOR, OR PLANS EXAMINER HAS ANY TECHNICAL QUESTIONS PLEASE CALL.
- INSTALLATION:POWERS LINTELS ARE TO BE INSTALLED IN ACCORDANCE WITH STANDARD CONSTRUCTIONS PRACTICES, SET TO PROPER LINE AND LEVEL, PLUMB AND TRUE, AND IN CORRECT RELATION TO OTHER WORK.
PowerBox8 STEEL LINTELSNOTE: NO SCALE 16 GAGE IS .060 INCHES THICK. 20 GAGE IS .039 INCHES THICK.

NOTES: PowerBox8 Lateral/Uplift – 16 and 20 Gauge
Florida - 3000psi
- PRODUCT NAME;PREFORMED POWERS STEEL LINTEL SHALL BE GALVANIZED COIL STEEL AS MANUFACTURED BY POWERS STEEL AND WIRE PRODUCTS, INC. STEEL GRADE SHALL BE ASTM A570 GRADE C (FY= 40 ksi).NOTE: DEFORMATIONS DO NOT EFFECT STRUCTURAL CAPACITY. FOR SPANS LESS THAN 16'-0" BOX LINTELS TO BE 20 GA. FOR SPANS GREATER THAN OR EQUAL TO 16'-0" BOX LINTELS TO BE 16 GA.
- SHORE LINTELS AS REQUIRED TO COMPENSATE FOR DEAD LOAD DEFLECTION ON NON-CURED MASONRY GROUT. ALL LINTELS GREATER THAN 18'-0" ARE BUILT WITH 1/2" CAMBER.
- LINTEL TO BE USED WITH BRICK OR CONCRETE MASONRY UNITS HAVING MINIMUM f’m AS SHOWN.
- STEEL SURFACES IN CONTACT WITH GROUT AND/OR MORTAR SHALL BE UNPAINTED AND FREE OF MATERIAL THAT MIGHT INHIBIT BOND.
- DESIGN BEARING OF POWERS STEEL LINTELS IS 8" FOR ALL LINTELS GREATER THAN 18'-0" IN SPAN OR GREATER THAN 32" IN DEPTH. ALL OTHER LINTELS REQUIRE A MINIMUM OF 4" BEARING PER THE STANDARD AND FLORIDA BUILDING CODES.
- f’m = 1500 psi. MASONRY UNITS SHALL CONFORM TO ASTM C90, GRADE N.
- GROUT = 3,000 psi. SLUMP RANGE: 8" TO 11". ROD OR VIBRATE GROUT ADEQUATELY TO ENSURE CONSOLIDATION OF GROUT (NO AIR POCKETS). GROUT SHALL COMPLY WITH ASTM C476-83 AND BE EITHER COARSE OR FINE GROUT.
- MORTAR: TYPE “S” OR TYPE “M” 1800 psi.
- TOP REINFORCING OR TOP OF WALL REINFORCING, IS REQUIRED BY CODES TO PROVIDE A CONTINUOUS TIE AROUND A STRUCTURE AND TO PROVIDE FOR UPLIFT RESISTANCE AT LINTELS.
- ATTACHMENTS TO TOP OF WALL PER ARCHITECTURAL AND/OR ENGINEERING DRAWINGS.
- LIMITATIONS:THE LINTELS SHALL NOT EXCEED THE ALLOWABLE DESIGN LOADS AND SPANS SHOWN IN THIS REPORT.THE LINTELS SHALL NOT BE USED IN A FIRE RESISTANCE RATED ASSEMBLY UNLESS A TEST REPORT DOCUMENTING FIRE RESISTANCE IS SUBMITTED TO THE BUILDING OFFICIAL.A PROPER BARRIER IS REQUIRED WHEN USING CORROSIVE LUMBER PRODUCTS IN CONTACT WITH THE STEEL LINTELS. A PROPER BARRIER WOULD BE A POLYETHYLENE BARRIER WITH A 10 MIL THICKNESS OR TO MAINTAIN A MIN. 1/4" SPACING BETWEEN THE CORROSIVE LUMBER AND STEEL LINTEL.
- ALLOWABLE LOADS SHOWN IN THE TABLES FOR UPLIFT AND LATERAL LOAD CAPACITY INCLUDE A 1/3 INCREASE FOR WIND OR SEISMIC LOADING WITH NO FURTHER INCREASES ALLOWED. TABLE VALUES SHOULD BE USED WITH ALTERNATE ALLOWABLE STRESS COMBINATIONS WITH A W OF 1.3. OTHERWISE REDUCE TABLE VALUES FOR ALLOWABLE STRESS COMBINATIONS BY 1/3. IF COMBINED LOADING CONDITIONS ARE APPLIED TO THE LINTELS FOR SIMULTANEOUS LOADING DIRECTIONS, THE ALLOWABLE LOADS SHOWN IN THE TABLES MUST BE ADJUSTED USING A UNITY EQUATION.
- ALL LOADS SHOWN IN TABLES ARE SUPERIMPOSED LOADS. TABLES ARE DATED 01/2021 AND CLEARLY INDICATE SUPERIMPOSED LOADS.
- #5 REINFORCING BAR(S) GRADE 40 IS TO SET APPROX. 1-1/2" FROM TOP OF ALL LINTEL DESIGNS AND IN SOME CASES THE BOTTOM OF LINTEL AS SHOWN ON LOAD TABLES. TOP HORIZONTAL REINFORCEMENT IS TO BE A CONTINUOUS TIE AS NOTED IN NOTE #9. IN THE CASE THAT THE LINTEL IS NOT WITHIN A COMPOSITE BOND BEAM SYSTEM, TOP HORIZONTAL REINFORCEMENT IS TO EXTEND 2'-0" PAST INSIDE OF JAMBS.
- MANUFACTURER:POWERS STEEL4118 E. ELWOOD PHOENIX, AZ 85040PHONE (602) 437-1160
- TECHNICAL DATA AND ENGINEERING POWERS LINTELS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE FOLLOWING:+ FLORIDA BUILDING CODE - 2020 (SEVENTH EDITION)+ AISI NORTH AMERICAN SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL - 2016+ TMS 402-16 TECHNICAL ASSISTANCE IS AVAILABLE FROM THE MANUFACTURER ON SPECIAL DESIGN CONCERNS OR LINTEL DEPTHS DIFFERENT THAN THOSE SHOWN IN THE LOAD TABLES. STRUCTURAL ENGINEER FOR THESE LINTELS IS: S.E. CONSULTANTS, INC. 5800 E. THOMAS RD. SUITE 104 SCOTTSDALE, AZ 85251 PHONE (480) 946-2010 FAX (480) 946-1909 IF AN INSPECTOR, CONTRACTOR, SUBCONTRACTOR, OR PLANS EXAMINER HAS ANY TECHNICAL QUESTIONS PLEASE CALL.
- INSTALLATION:POWERS LINTELS ARE TO BE INSTALLED IN ACCORDANCE WITH STANDARD CONSTRUCTIONS PRACTICES, SET TO PROPER LINE AND LEVEL, PLUMB AND TRUE, AND IN CORRECT RELATION TO OTHER WORK.
PowerBox8 STEEL LINTELS NOTE: NO SCALE 16 GAGE IS .060 INCHES THICK. 20 GAGE IS .039 INCHES THICK.

- Request Quote
- PowerBox Benefits
- PowerBox8 Florida Load Tables
- PowerBox8 Florida Engineering Notes
- PowerBox8 Miami Dade Load Tables
- PowerBox8 Miami Dade Engineering Notes
- Recessed Door Header Load Tables
- Recessed Door Header Engineering Notes
- Details & Drawings
- Installation
- Box Lintel vs. Precast
- Independent Corrosion Report
- Dealers